Variable-Speed Control and Energy Efficiency for Biogas Blowers

Variable-speed control and energy efficiency for biogas blowers depend on how machine capacity follows demand and system resistance. Feedstock loading, digester temperature, biological activity, gas-storage level and downstream demand can all change the required gas flow.

CHP engines may reduce load or stop for maintenance. Boilers and flares operate intermittently. Biomethane upgrading systems may run in scheduled cycles. Landfill-gas collection systems also experience changing gas production and wellfield conditions.

A fixed-speed blower selected for the maximum flow may therefore spend much of its operating life producing more capacity than the process requires. If this excess flow is continuously recycled through a bypass valve, the plant consumes energy without delivering useful gas.

Variable-frequency-drive control allows the blower speed to follow the actual process demand. When properly designed, it can reduce unnecessary power consumption, stabilize gas pressure and improve control. However, the achievable savings depend on blower type, system pressure, turndown range and operating profile.

Flow, Speed and Power Relationships

A roots blower is a positive-displacement machine. Its rotors transfer an approximately fixed geometric volume during each revolution.

The theoretical relationship between displacement, speed and inlet flow can be expressed as:

Blower Capacity and Rotational Speed

Qactual  ≈  Vd  ×  N  ×  ηv
At comparable differential pressure and gas conditions:
Q2
Q1
 ≈ 
N2
N1
where:
  • Qactual = actual blower inlet volume flow
  • Vd = geometric displacement per revolution
  • N = rotational speed
  • ηv = volumetric efficiency
  • Q1 and Q2 = blower capacities at two operating points
  • N1 and N2 = corresponding rotational speeds

This relationship explains why speed control is an effective method of regulating roots blower capacity. Reducing speed reduces the amount of gas displaced per unit time.

The relationship is not perfectly linear in real operation. Internal leakage represents a larger proportion of theoretical displacement at low speed, while clearances, gas temperature and differential pressure also influence volumetric efficiency.

The theoretical gas power for a low-pressure roots blower can be approximated by:

Theoretical Gas Power and Shaft Power

Ptheoretical  =  Qactual  ×  Δp
A preliminary shaft-power relationship is:
Pshaft  ≈ 
Qactual  ×  Δp
ηoverall
where:
  • Ptheoretical = theoretical gas power
  • Qactual = actual inlet flow in m³/s
  • Δp = blower differential pressure in Pa
  • Pshaft = approximate shaft power
  • ηoverall = combined efficiency used for the preliminary estimate

At approximately constant differential pressure, reducing speed and flow may produce an approximately proportional reduction in theoretical power. Actual electrical power will also include blower mechanical losses, motor losses and VFD losses.

The cubic fan law should not be applied automatically. For a centrifugal fan operating in a system dominated by dynamic resistance:

Affinity Laws (Speed Relationships)

•   Q  ∝  N
•   Δp  ∝  N2
•   P  ∝  N3

A roots blower behaves differently because it transfers a substantially fixed volume per revolution and develops the pressure imposed by the downstream system. If the process maintains nearly constant pressure, its power does not normally decrease according to the cube of speed.

If system resistance falls substantially when flow is reduced, the roots blower’s differential pressure may also decrease. In that case, power can fall faster than the speed ratio alone would indicate. Energy savings must therefore be calculated from the actual system curve and measured operating profile.

VFD, Bypass and Multiple-Blower Control

A variable-frequency drive changes the electrical frequency and voltage supplied to the motor, allowing the blower speed to follow a process signal.

Possible control variables include:

  • Gas-header pressure
  • Digester headspace pressure
  • Gas-holder level
  • Blower suction pressure
  • Downstream consumer demand
  • Biogas flow
  • Vacuum setpoint
  • Upgrading-plant production rate

The selected control variable should represent the true process requirement. Maintaining an unnecessarily high discharge pressure wastes energy even if the blower uses an efficient motor and VFD.

For gas boosting, the VFD may control the discharge-header pressure. For extraction duty, it may control the suction pressure or vacuum. In digester systems, the control philosophy must prevent excessive pressure and excessive vacuum independently of normal blower regulation.

Gas storage provides a useful buffer between production and consumption. Instead of forcing the blower to respond to every small flow fluctuation, the control system can operate within an approved storage-pressure or membrane-position band. This reduces frequent speed changes and improves control stability.

VFD control offers several advantages:

  • Continuous capacity adjustment
  • Reduced dependence on bypassing
  • Lower startup current
  • Controlled acceleration and deceleration
  • Improved pressure stability
  • Compatibility with remote process control
  • Easier coordination of multiple blowers

The VFD does not eliminate the need for a differential-pressure relief valve. A blocked discharge, closed valve or control-system failure can still expose the blower to excessive pressure.

Bypass or recycle control redirects discharge gas to the blower inlet. It provides rapid protection and can maintain temporary operation when downstream demand falls suddenly. However, it does not provide the same energy benefit as reducing speed.

During bypass operation, the blower continues to compress the recycled gas. The recycle stream returns warmer than the original suction gas and may pass through the blower repeatedly. Prolonged bypassing can therefore create:

  • High suction temperature
  • Excessive discharge temperature
  • Increased absorbed power
  • Reduced gas density
  • Seal and elastomer stress
  • Lubricant deterioration
  • Automatic high-temperature shutdown

A bypass valve should primarily serve pressure protection, transient control or a defined minimum-flow requirement. Continuous recycling should be evaluated thermally and economically. Where long-term recycle is unavoidable, a gas cooler may be required.

Inlet throttling is generally inefficient for controlling a positive-displacement blower. Restricting the suction does not directly change the geometric displacement. Instead, it lowers the absolute inlet pressure and can increase the pressure ratio and discharge temperature.

For plants with a wide flow range, multiple-blower control may be more efficient than operating one oversized blower at very low speed. Possible arrangements include:

  • One VFD-controlled blower
  • One fixed-speed base-load blower and one VFD trim blower
  • Two or more staged blowers
  • Duty-and-standby blowers
  • Several equal-sized units operating sequentially
  • Unequal-sized units selected for the plant load profile

A base-and-trim strategy allows one blower to operate near an efficient duty point while a smaller variable-speed unit follows the changing demand. When demand rises, another blower starts and the trim unit adjusts to maintain pressure.

The control system should prevent inefficient operating combinations, such as running several large blowers simultaneously at their lowest permitted speeds when fewer machines could meet the demand more efficiently.

Glossary

Bypass control: Capacity-control method that recirculates or diverts part of the gas flow.
Flow-speed relationship: Approximate relation between blower speed and actual volumetric flow within machine limits.
Gas-holder pressure: Pressure in the storage vessel that buffers biogas generation.
Load-following response: How quickly blower flow adjusts to a change in process gas demand.
Specific energy: Electrical energy consumed per unit of gas transferred.
Speed-control range: Permitted range between minimum and maximum operating speed for the installed drive.
Turndown: Reduction from rated capacity while remaining within stable operating limits.
VFD: Variable-frequency drive used to adjust motor speed and machine capacity.